Page 22
HydroRanger 200 – INSTRUCTION MANUAL
7ML19985FC03
mmmmm
Ope
rat
ion
Icons indicating index type (Item 1) edited in PROGRAM mode:
Readings in RUN Mode
Change the displayed values with the keys on the hand programmer. All readings are
shown in the Auxiliary field, except for the totalizer and P920.
Icon
Index Type
measurement point or transducer
relay
secondary index
mA input or output
Key
Function
P#
Toggle Readings between percent and units:
• Level: 0 – 100%
• Space or Distance:
1
100% – 0
1.
Distances less than 0.3 m (1 ft) from the transducer face cannot be measured
reliably. Therefore, a 0% reading is not possible during Distance operation.
P920
+
Accumulated pump running hours
2
for numbered pump.
2.
If the associated relay is programmed for pump control.
P310
+
Hold number key for five seconds to display the number of
accumulated pump starts
2
for numbered pump.
P311
[6 relay model]
Eight-digit totalizer, uses index and reading areas, press
again to toggle, P737 sets default.
Used for OCM and Pumped Volume.
P322
P323
P920
[6 relay]
Head measurement
P926
[6 relay]
Instantaneous flow based on head (OCM)
P925
mA Output value
P203
Temperature
P664
Rate of level change
P707
Failsafe Time Left (in %). When the Reading is updated,
this value (Auxiliary Reading) resets to 100 and begins to
decrease until the next valid measurement is made. If the
Failsafe Time Left reaches 0, LOE flashes in the display.
Hold for four seconds to show echo confidence
P805
+ ###
Display the value of the entered parameter which is global
or indexed by transducer
Auxiliary reading displays parameter specified in P731
P731
Distance
P923
P
P