Set Relays to FIXED DUTY BACKUP
[6 relay model]
Set the Relay ON Setpoints [6 relay model]
Set the Relay OFF Setpoints [6 relay model]
Set Relays to ALTERNATE DUTY SERVICE [6 relay model]
Set the Relay ON Setpoints [6 relay model]
Set the Relay OFF Setpoints
[6 relay model]
Parameter
Index
Value
Description
P111
1
51
Sets the pump relays (index 1, 2, and 3) to
FIXED DUTY BACKUP. Only one pump will
ever run at one time.
P111
2
51
P111
3
51
Parameter
Index
Value
Description
P112
1
0.4m
Sets the three setpoints for the pump relays.
The setpoints remain attached to the pump
relays.
P112
2
0.3m
P112
3
0.2m
Parameter
Index
Value
Description
P113
0
1.3m
By using index 0 all six relays are set at the
same time, including any alarm relays. Use
with caution.
Parameter
Index
Value
Description
P111
1
54
Sets the pump relays (index 1, 2, and 3) to
SERVICE RATIO DUTY ASSIST
P111
2
54
P111
3
54
P122
1
25
Sets the ratio to: 25% – Pump One
50% – Pump Two
25% – Pump Three
P122
2
50
P122
3
25
Parameter
Index
Value
Description
P112
1
0.4m
Sets the three setpoints for the pump relays.
The first cycle will use these setpoints.
Subsequent cycles rotate the setpoints
among the pumps.
P112
2
0.3m
P112
3
0.2m
Parameter
Index
Value
Description
P113
0
1.3m
By using index 0 all six relays are set at the
same time, including any alarm relays. Use
with caution.