7ML19985FC03
HydroRanger 200 – INSTRUCTION MANUAL
Page 177
mmm
mm
Pa
ra
m
e
te
rs
Enter the factor (powers of 10 only) by which actual volume is divided, prior to Remote
Totalizer count increment.
Example:
For a Remote Totalizer update by 1000s of volume units, enter 3.
P641 Flow Sampler Mantissa [6 relay model]
Use this feature in conjunction with Flow Sampler Exponent (P642) to establish the
number of flow units required to increment the Flow Sampler (device connected to the
HydroRanger 200 relay set for the flow sampler operation Relay Function, P111 = 41).
This parameter is relevant only if Operation is set to OCM (P001 = 6).
Enter the mantissa (Y) for the exponent (Z) in the formula:
Flow Sampler Increment = Y x 10
Z
Flow units.
Example:
To count once every 4310 (4.31 x 10
3
) flow units:
•
set P641 to 4.31 and P642 to 3
P642 Flow Sampler Exponent [6 relay model]
Use this feature in conjunction with Flow Sampler Mantissa (P641) to establish the
number of flow units required to increment the Flow Sampler (device connected to the
HydroRanger 200 relay set for the flow sampler operation Relay Function, P111 = 41).
Primary Index
Single Point Model
Dual Point Model
Global
Transducer
Values
Range: 0.001 to 9999
Preset = 1.000
Related
•
P001 Operation
•
P111 Relay Control Function
•
OCM (P600 to P621)
•
P642 Flow Sampler Exponent
Primary Index
Single Point Model
Dual Point Model
Global
Transducer
Values
Range: -3 to +7 (integers only)
Preset = 0
Related
•
P001 Operation
•
P111 Relay Control Function
•
OCM (P600 to P621)
•
P641 Flow Sampler Mantissa
Summary of Contents for HydroRanger 200
Page 1: ...Instruction Manual July 2009 200 hydroranger ...
Page 232: ...Page 222 HydroRanger 200 INSTRUCTION MANUAL 7ML19985FC03 mmmmm Parameters Notes ...
Page 264: ...Page 254 HydroRanger 200 INSTRUCTION MANUAL 7ML19985FC03 mmmmm Appendix H Software Rev Notes ...
Page 278: ...Notes ...
Page 279: ......