HydroRanger 200 – INSTRUCTION MANUAL
7ML19985FC03
mmm
mm
Pa
ra
m
e
te
rs
P005 Units
Specifies measurement units used for dimensional values.
Changing this value automatically changes the units displayed for many parameters.
Existing values are converted and do not have to be re-entered.
P006 Empty
Enter distance in units (P005) from the face of the transducer to the process empty point.
Setting this value also sets Span (P007) unless Span was already set to another value.
For distance operation (P001=3), Span is preset to Empty.
Related
(chart cont’d from
previous page)
•
P203 mA Output Value/Transducer
•
mA Input (P250 to P260) (related only to Value 250)
•
P800 Near Blanking
•
P823 Reform Echo
•
P832 TVT Shaper Adjust
•
P840 Short Shot Number
•
P841 Long Shot Number
•
P842 Short Shot Frequency
•
P843 Long Shot Frequency
•
P844 Short Shot Width
•
P845 Long Shot Width
•
P852 Short Shot Range
Primary Index
Global
Values
1
*
Meters
2
Centimeters
3
Millimeters
4
Feet
5
Inches
Alters
•
P006 Empty
•
P007 Span
•
P603 Maximum Head
•
P605 Zero Head
•
P620 Low Flow Cutoff
•
P921 Material Measurement
•
P926 Head Measurement
•
P927 Distance Measurement
Primary Index
Transducer
Values
Range: 0.000 to 99.000 m (or equivalent depending on units)
Preset: 5.000 m (or equivalent depending on units)
Alters
•
P007 Span
Altered By
•
P005 Units
Related
•
P800 Near Blanking
•
P921 material Measurement
•
P927 Distance Measurement