Alarms
Setting Simple Level Alarms
To set Relay Five to a standard level alarm (Hi Hi, Hi, Lo, Lo Lo) do the following:
Available designations:
Rate [6 relay model]
Rate alarms can trigger an alarm if the vessel is filling/emptying too quickly.
Setting a Filling Rate Alarm
Setting an Emptying Rate Alarm
Parameter Index Value Description
P110
5
1
•
Set P110, indexed to relay, to the value 1 for
Transducer One
P111
5
1
•
Set P111, indexed to relay, to the value
1
for level
alarm
•
Press UNIT
to display the Auxiliary Function
symbol.
•
Press ARROW keys
as required to scroll
to the alarm designation (L, LL, H, or HH).
•
Press ENTER
to enter the value.
P112
5
1.2m •
Set the
ON
setpoint
P113
5
1.15m •
Set the
OFF
setpoint
Alarm
Designation
Hi Hi
HH
Hi
H
Lo
L
Lo Lo
LL
Parameter
Index
Value Description
P111
5
4
These settings trip the alarm when the
reservoir is filling faster than 1m per minute
and reset it at 0.9m per minute.
P112
5
1m
P113
5
0.9m
Parameter
Index
Value
Description
P111
5
4
These settings trip the alarm when the
reservoir is emptying faster than 10% of span
per minute and reset the alarm when
emptying falls to 5%.
P112
5
-10%
P113
5
-5%