Page 140
HydroRanger 200 – INSTRUCTION MANUAL
7ML19985FC03
mmm
mm
Pa
ra
m
e
te
rs
Relay Failsafe is only available for the following relay functions (P111) and is not used for
any other relay control function.
To select an independent Relay Failsafe value:
1.
Press FUNCTION
to display the Auxiliary Function symbol.
2.
Press ARROWS
to scroll through the failsafe options.
3.
Select option and press ENTER
.
Advanced Pump Control Modifiers (P130 to P137)
[6 relay model]
Please note that these parameters apply to the HydroRanger 200 6 relay model only.
These parameters only affect relays set to pump operation (P111 = 50 to 56).
P130 Pump Run-On Interval [6 relay model]
Sets the number of hours between pump run-on occurrences.
To clear sediment in a
pump-down
wet well, run the pump after the normal OFF setpoint
is reached to force some solid material through. This parameter sets the time between
such events. Only the last pump running can run-on.
Relay Function (P111)
Preset (P129)
1 – level alarm
OFF
2 – in bounds alarm
3 – out of bounds alarm
4 – rate of change alarm
5 – temperature alarm
50 to 56 – all pump controls
dE
Primary Index
Global
Values
Range: 0.000 to 1000
Preset: 0.000
Related
•
Advanced Pump Control Modifiers (P130 to P136)