HydroRanger 200 – INSTRUCTION MANUAL
7ML19985FC03
mmm
mm
Pa
ra
m
e
te
rs
P913 Sensor Temperature
Access this parameter to display the temperature in °C (as monitored by the TS-3).
OPEn is displayed if a TS-3 is not connected.
P914 mA Input [6 relay model]
Use this feature to display the mA input value (in mA).
Measurement (P920 to P927)
All of these parameters are available in RUN mode and used to verify programming. See
Readings in RUN Mode
on page 22.
The range and values shown for each of these parameters depends on the Operation
(P001) chosen. The readings for each operation are listed below.
To Access in RUN Mode
1.
Ensure the device is in RUN mode.
2.
Press
.The Auxiliary Reading field becomes underscores P_ _ _
3.
Type the parameter number. The field changes to the value of the specified
parameter.
These parameters are also available in simulation mode. See the
Testing the
Configuration
section page 83 for instructions on how to control the simulation direction
and rate.
P920 Reading Measurement
Corresponds to the final reading after all programming is applied.
Please note that the following features apply only to the HydroRanger 200 6 relay model:
Difference, Average, OCM, and Pump Totalizer.
In general this means that: P920 = (Reading x P061) + P062.
Primary Index
Global
Values
Range: -50 to 150
Primary Index
mA input
Values
Range: 0.000 to 24.00
Primary Index
Level
Values
Range: -999 to 9999