7ML19985FC03
HydroRanger 200 – INSTRUCTION MANUAL
Page 145
mmm
mm
Pa
ra
m
e
te
rs
mA Output (P200 to P219)
P200 mA Output Range
Determines the mA output range.
If either 1 or 2 is selected, the mA output is directly proportional to the mA Function. If
either 3 or 4 is selected, then the output is inversely proportional. After setting P200,
verify that P212 has a valid entry for mA Output Min Limit, as P212 is not changed
automatically by a change to P200.
P201 mA Output Function
Alters the mA output/measurement relationship.
Please note that parameter P201 values vary between the HydroRanger 200, 1 or 3 relay
model, and the HydroRanger 200, 6 relay model.
HydroRanger 200 [1 or 3 relay model]
Primary Index
mA output
Values
0
off
1
0 to 20 mA
2
*
4 to 20 mA
3
20 to 0 mA
4
20 to 4 mA
Related
•
P911 mA Output Value
Primary Index
mA output
Values
value
mA function
Operation (P001)
0
OFF
1
level
level
2
space
space
3
distance
distance
Related
•
P202 mA Output Allocation
•
P911 mA Output Value
Altered By
•
P001 Operation