Page 44
HydroRanger 200 – INSTRUCTION MANUAL
7ML19985FC03
mmmm
m
Relay
s
Preset Applications
Preset applications set up the relay parameters to predetermined values shown below:
Value
# Parameters Affected
Off
0 All relays set to OFF
Wet Well 1
1
Pump down with the following settings:
Parameter
Relay #
1
2
3
4
5
6
P111
52
52
1(H)
1(L)
0
0
P112
70%
80%
90%
10%
–
–
P113
20%
20%
85%
15%
–
–
Wet Well 2
2
Pump down with the following level and rate settings:
Parameter
Relay #
1
2
3
4
5
6
P111
52
52
1(H)
1(L)
0
0
P112
70%
80%
90%
10%
–
–
P113
20%
20%
85%
15%
–
–
P121
1
P121 sets the pump relays to accept control by rate of level change once
the first ON setpoint is reached. Because the pumps are started by rate,
you must change P703 to desired empty rate.
Reservoir 1
3
Pump up with the following level settings:
Parameter
Relay #
1
2
3
4
5
6
P111
52
52
1(H)
1(L)
0
0
P112
30%
20%
90%
10%
–
–
P113
80%
80%
85%
15%
–
–
Reservoir 2
4
Pump up with the following level and rate settings:
Parameter
Relay #
1
2
3
4
5
6
P111
52
52
1(H)
1(L)
0
0
P112
20%
20%
90%
10%
–
–
P113
80%
80%
85%
15%
–
–
P121
1
P121 sets the pump relays to accept control by rate of level change once
the first ON setpoint is reached. Because the pumps are started by rate
you must change P702 to desired fill rate.
Screen
5
Differential control of a screen or rake:
Parameter
Relay #
1
2
3
4
5
6
P110
3
1
2
3
0
0
P111
50
1(H)
1(L)
1(H)
–
–
P112
80%
90%
10%
90%
–
–
P113
20%
85%
15%
10%
–
–
Alarms
6
General alarms at four setpoints:
Parameter
Relay #
1
2
3
4
5
6
P111
1(H)
1(L)
1(HH)
1(LL)
0
0
P112
80%
20%
90%
10%
–
–
P113
75%
25%
85%
15%
–
–