P805 Echo Confidence
Displays the echo confidence of the measurement echo from the last shot.
Use this feature to monitor the effect of transducer aiming, location, and mechanical
transducer / mounting isolation.
Both short and long shot Echo Confidence is displayed. (To display this value in the
auxiliary display while the unit is running, press
for 4 seconds.)
P806 Echo Strength
Displays the strength (in dB above 1 uV RMS) of the echo which was selected as the
measurement echo.
P807 Noise
Displays the average and peak ambient noise (in dB above 1 uV RMS) being processed.
The noise level is a combination of transient acoustic noise and electrical noise (induced
into the transducer cable or receiving circuitry). See
Noise Problems
in the
Troubleshooting
Section on page 232.
Primary Index
Transducer
Values
Format: x:y (view only)
x = short (0 to 99)
y = long (0 to 99)
Related
•
P804 Confidence Threshold
•
P830 TVT Type
Display
Description
x:--
short shot confidence value, (long shot not used).
--:y
long shot confidence value, (short shot not used).
x:y
short and long shot confidence values (both used).
E
transducer cable is open or short circuited.
--:--
no shots were processed for Sonic Intelligence® evaluation.
Primary Index
Transducer
Values
Format: 0 to 99 (view only)
Primary Index
Transducer
Values
Format: x:y (view only)
x = average (-99 to 99)
y = peak (-99 to 99)