7ML19985FC03
HydroRanger 200 – INSTRUCTION MANUAL
Page 23
m
mmmm
Oper
a
tion
Status Parameters
Status parameters give the operating status of the HydroRanger 200. You can access
parameters with the hand programmer (see page 31) or with Dolphin Plus (see page 26).
Remote SCADA system access is also possible.
Parameter
Values
P203
mA Output Value
0 to 22 – Current mA output
P254
[6 relay
model]
Scaled mA Input Value
0 to 9999 – Current mA input after scaling
P275
Scaled Discrete Input Value Shows current value of discrete input,
values vary by DI function
P322
[6 relay
model]
LCD Total Low
The last four digits of the totalizer
P323
[6 relay
model]
LCD Total High
The first four digits of the totalizer
P341
Run Time
The number of days the HydroRanger 200
has been operating
P342
Start Ups
The number of times power has been
cycled
P664
Temperature
Current temperature measured by
transducer
P707
Rate Value
Current rate of material level change
P708
[6 relay
model]
Volume Rate Display
Current rate of material volume change
P729
Scan Time
Seconds since last level scan
P806
Echo Strength
Strength of primary echo
P920
Reading Measurement
Current primary reading
P921
Material Measurement
Current level from P007–Span
P922
Space Measurement
Empty space above the material level
P924
[6 relay
model]
Volume Measurement
Current volume value, if programmed
P925
[6 relay
model]
Flow Measurement (OCM) Current flow value, if OCM programmed
P926
[6 relay
model]
Head Measurement (OCM) Current level, if OCM programmed
P927
Distance Measurement
Distance from transducer face to material
Summary of Contents for HydroRanger 200