P608 Flowrate Units [6 relay model]
The volume units used to display total flow.
This parameter is enabled only if the primary measuring device (PMD) supports absolute
calculations (P600=6,7). For absolute PMDs (P600=6,7) volume units can be specified
using this parameter. If needed, absolute PMDs can still use ratiometric (P608=0) to
accommodate other units.
Note:
Set this parameter only when using BS-3680/ISO 4359 Rectangular Flume
or BS-3680/ISO 1438/1 Thin Plate V-Notch Weir (P600 = 6 or 7). Use the default
value of 0 for P608 when P600 = 1 to 5.
Primary Index
Single Point Model
Dual Point Model
Global
Transducer
Values
Ratiometric (P600=all)
0
*
Ratiometric calculation (units defined by P604)
Absolute (P600=6,7 only)
1
litres / second
2
cubic metres / hour
3
cubic metres / day
4
cubic feet / second
5
gallons / minute – Imperial
6
million gallons / day – Imperial
Values
7
gallons / minute – U.S.
8
million gallons / day – U.S.
Alters
•
P606 Time Units
Altered By
•
P600 Primary Measuring Device
Related
•
P608 Flowrate Units