P110 Level Source [6 relay model]
Sets the level source on which the indexed relay is assigned to a measurement point.
Please note that Difference and Average settings are features of the HydroRanger 200
6 relay model.
HydroRanger 200 [6 relay model]
Please note that these features are only available on the HydroRanger 200 6 relay model.
In Single Point Mode (standard):
Points 2 and 3 are available only if Operation is set for difference or average
(P001 = 4 or 5).
In Dual Point Mode (optional):
Point 2 is always available, and Point 3 is available only if Operation is set for difference or
average (P001 = 4 or 5).
P111 Relay Control Function
Sets the control algorithm used to trip the relay.
Please note that parameter P111 values vary between the HydroRanger 200, 1 or 3 relay
model and the HydroRanger 200, 6 relay model.
Use zero
0
(preset) to disable control of the indexed relay.
Primary Index
Relay
Values
Range: 1 to 3
1
* Point # 1 = Transducer One
2
Point # 2 = Transducer Two
3
[6 relay
model]
Point # 3 = Difference (P001=4) or Average (P001=5)
[6 relay model]
Altered by:
•
P003 Maximum Process Speed
•
P700 Max Fill rate
•
P701 Max Empty rate
•
P070 Failsafe Timer
•
P071 Failsafe Material Level
Primary Index
Relay
Values
See chart below
Altered by
•
P100 Preset Applications
Note:
All relay ON/OFF points must be referenced from Empty (P006), regardless
of Operation Mode selection (POO1).