HydroRanger 200 – INSTRUCTION MANUAL
7ML19985FC03
mmm
mm
Pa
ra
m
e
te
rs
HydroRanger 200 [1 or 3 relay model]
HydroRanger 200 [6 relay model]
Values For P111
Control
Type
#
1
1.
When reading and setting this parameter through Modbus or SmartLinx
communications the parameter values are mapped to different numbers.
See
HydroRanger 200 Communications
on page 87 for Modbus informa-
tion or the relevant SmartLinx
®
manual.
Relay Control
General
OFF
0* Relay set off, no action (preset)
Level
1 Based on level setpoints ON and OFF
Loss of Echo (LOE)
6 When echo is lost
Cable Fault
7 When the circuit to a transducer is opened
Pump
Fixed Duty Assist
50
At fixed ON and OFF setpoints and allows multiple
pumps to run
Alternate Duty
Assist
52
At rotating ON and OFF setpoints and allows multiple
pumps to run
Communication
65
Based on input from external communications. See
Communications
section on page 87 for further refer-
ence.
Values For P111
Control
Type
#
1
Relay Control
General
Off
0* Relay set off, no action (preset)
Level
1 Based on level setpoints ON and OFF
In Bounds
2
When level enters the range between ON and OFF
setpoints
Out of Bounds
3
When level exits the range between ON and OFF set-
points
Rate of Change
4 Based on rate setpoints ON and OFF
Temperature
5 Based on temperature setpoints ON and OFF
Loss of Echo (LOE)
6 When echo is lost
Cable Fault
7 When the circuit to a transducer is opened
Flow
Totalizer
40 Every 10
y
units
(P641-P645)
Flow Sampler
41 Every y x 10
Z
units (P641-P645) or time duration (P115)