P336 Auto Record Filling / Emptying
Use this feature to restrict Auto Profile Records from being saved unless the level is
rising, falling or either.
If the level changes at a rate in excess of the corresponding Filling / Emptying Indicator
(P702 / P703) values, the Echo Profile is saved subject to this and other Auto Profile
Record restrictions.
P337 Auto Record LOE Time
Limits Auto Profile Records from being saved unless extended LOE occurs.
If the LOE condition exceeds the period entered, the Echo Profile is saved. When set for 0
LOE is not required for an Auto Profile Record to be saved.
Primary Index
Global
Values
0
*
Auto Profile Record on filling or emptying
1
Auto Profile Record on filling only
2
Auto Profile Record on emptying only
Related
•
P334 Auto Record ON Setpoint
•
P335 Auto Record OFF Setpoint
•
P337 Auto Record LOE Time
•
P702 Filling Indicator
•
P703 Emptying Indicator
Primary Index
Global
Values
Range: 0.0 to 9999 (seconds)
Preset: 0.0
Related
•
P334 Auto Record ON Setpoint
•
P335 Auto Record OFF Setpoint
•
P336 Auto Record Filling / Emptying