HydroRanger 200 – INSTRUCTION MANUAL
Page 75
m
mmmm
Open Channel Monit
oring
6 Relay Model
Palmer Bowlus Flume
Application Information
•
Sized by pipe diameter D
•
Flume relief is trapezoidal
•
Designed to install directly into pipelines and manholes
•
Head is referenced to bottom of the throat, not bottom of the pipe
•
For rated flows under free flow conditions, the head is measured at a distance of
D/2 upstream from the beginning of the converging section
(view only)
6
Discharge coefficient (Cd)
(view only)
7
Cross sectional area
P605
G
Zero Head
P608
G
Flowrate Units
Parameter
Index
Value
P600
G
2–Palmer Bowlus Flume
P602
1
Flume width (D)
P603
G
Maximum Head (preset = P007)
P604
G
Maximum Flow
P605
G
Zero Head
P606
G
Time Units
Parameter
Index
Value
P006
P007
P605
P603
Transducer
D/2, point of
measurement
Flow
Plan View
Front View
Side View