7ML19985FC03
HydroRanger 200 – INSTRUCTION MANUAL
Page 81
m
mmmm
Open Channel Monit
oring
6 Relay Model
Universal Calculation Support
When the primary measuring device (PMD) doesn’t fit one of the standard types, it can
be programmed using a universal characterization. When Universal is selected as the
PMD type (P600), then both P610 and P611 must be entered to define the flow.
Two curve types are supported:
•
P600 = 4–linear (piece wise linear)
•
P600 = 5–curved (cubic spline)
Both are shown in the following chart.
Typical Flow Characterization
Characterization is achieved by entering the head (P610) and corresponding flow (P611),
either from empirical measurement or from the manufacturer's specification. Increasing
the number of defined breakpoints will increase the accuracy of the flow measurement.
Breakpoints should be concentrated in areas exhibiting the higher degrees of non linear
flow. A maximum of 32 breakpoints can be defined. The curve’s end point is always
specified by the parameters Maximum Head (P603) and Maximum Flow (P604) for a
maximum total of 33 breakpoints.
Use as many breakpoints as required by the complexity of your PMD.
See
Volume
on page 49 for more information and parameters P610 and P611 for
characterization.
Maximums (P603, P604)
Linear
Curved
Head (P610)
Fl
ow
(P
61
1)
Max. Flow
Zero Flow
Zer
o H
ead
Max.
Hea
d
Head Breakpoints
Fl
ow
Br
ea
kp
oi
nts
Summary of Contents for HydroRanger 200
Page 1: ...Instruction Manual July 2009 200 hydroranger ...
Page 232: ...Page 222 HydroRanger 200 INSTRUCTION MANUAL 7ML19985FC03 mmmmm Parameters Notes ...
Page 264: ...Page 254 HydroRanger 200 INSTRUCTION MANUAL 7ML19985FC03 mmmmm Appendix H Software Rev Notes ...
Page 278: ...Notes ...
Page 279: ......