Page 146
HydroRanger 200 – INSTRUCTION MANUAL
7ML19985FC03
mmm
mm
Pa
ra
m
e
te
rs
HydroRanger 200 [6 relay model]
P202 mA Output Allocation
Sets the input source from which the mA output is calculated.
Please note that parameter P202 values vary between the HydroRanger 200, 1 or 3 relay
model, and the HydroRanger 200, 6 relay model.
HydroRanger 200 [1 or 3 relay model]
HydroRanger 200 [6 relay model]
Primary Index
mA output
Values
value
mA function
Operation (P001)
0
OFF
1
level
level, differential, or average
2
space
space
3
distance
distance
4
volume
level or space
5
flow
OCM
6
head
7
volume rate
8
mA input
9
comms input
Related
•
P202 mA Output Allocation
•
P911 mA Output Value
Altered By
•
P001 Operation
Primary Index
mA output
Values
1
*
Point 1
Related
•
P201 mA Output Function
Primary Index
mA output
Values
1
*
Point 1
2
Point 2
1:2
Average of readings from Point 1 and Point 2
3
Point 3
Related
•
P201 mA Output Function