Please note the following:
•
enter value in current units (as selected in P005)
•
valid for level, space, and distance
•
volume is calculated based on the Backup level
Example:
Transducer One is configured for a level measurement. Digital Input 2 is connected to a Hi
Level Backup switch located a level of 4.3m.
When the level rises to 4.3m, and the switch is activated, the reading is forced to 4.3m.
The reading stays at 4.3m until the switch is de-activated.
P066 Override Time Delay
Defines the time used to calm (debounce) the override condition input. Set in seconds.
P069 Password
Holds the current password for P000. Select by typing in 069. You cannot scroll to this
parameter.
This parameter is write-only, and can only be selected by entering 069. To change the
password, unlock the device by entering the current password into P000. Then enter the
new password into P069. To lock the device, enter a password other than the correct one
in P000. While the device is unlocked, the password is visible in P000.
Parameter
Index
Value
P064
1
2
P065
1
4.3
Primary Index
Transducer
Values
Range: 0.0 to 9999
Preset: 5.0
Related
•
P064 Override Enable
•
P065 Reading Override Value
•
P270 Discrete Input Function
Note: Activation of the Level Override is subject to the measurement cycle. This
can add up to four seconds to the overall response time depending on operating
conditions and programming.
Primary Index
Global
Values
Range: 0 to 9999
Default: 1954
Related
•
P000 Lock