Page 10
HydroRanger 200 – INSTRUCTION MANUAL
7ML19985FC03
mmm
mm
Inst
allat
ion
Cable routed through a conduit:
1.
Remove the four mounting screws holding the motherboard to the enclosure.
2.
Be careful not to damage the electronics with static electricity. Remove the
motherboard from the enclosure by pulling the board straight out.
3.
Drill the required cable entry holes. Make sure conduit holes do not interfere with
the lower areas on the terminal block, circuit board, or SmartLinx card.
4.
Attach the conduit to the enclosure using only approved suitable size hubs for
watertight application.
5.
Reinstall the motherboard with the mounting screws.
.
Cable exposed and entering through the cable glands:
1.
Unscrew the glands and attach them loosely to the enclosure.
2.
Thread the cables through the glands. Ensure the power cable is kept separated
from the signal cables and then wire the cables to the terminal blocks.
3.
Tighten the glands to form a good seal.
Note: For conduit locations and assembly for hazardous mounting in Class 1 Div 2
applications, please see Drawing 23650314 in
Appendix G: Conduit Entry for Class
1, Div 2 Applications
on page 249.
Note:
Where more holes are required than are supplied in the enclosure, follow
the
Cable routed through a conduit
steps.
suitable location for conduit entrances