Appendix E: Updating Software
Updating Software
To update the software in the HydroRanger 200, please contact your Siemens Milltronics
representative to obtain the software. For a complete list of representatives, go to
www.siemens.com/processautomation.
To install the software, please complete the following:
1.
Connect your PC or laptop to the HydroRanger 200 RJ-11 RS-232 port.
2.
Run the .exe Downloader program in the software. Use this to set the RS-232
settings to match your HydroRanger 200. Please note that the software default
settings will already match the default settings of the unit. Changes are only
necessary if the RS-232 settings in the unit have been changed.
3.
Complete the Downloader program steps.
4.
Verify that Downloader confirms a succesful upgrade before exiting.
5.
Complete a Master Reset (P999) after a successful upgrade, before re-entering
parameters.
WARNINGS:
1. All parameter values will be lost during software upgrade.
Record your current parameters manually or using Dolphin Plus or
SIMATIC PDM before upgrade.
2. Disable all pumps and alarms before updating software, as
relays can change state during the software update causing pumps
to turn on or off .