7ML19985FC03
HydroRanger 200 – INSTRUCTION MANUAL
Page 217
mmm
mm
Pa
ra
m
e
te
rs
P908 Scanner
Press ENTER
to cycle the scanner relay while firing the transmitter.
Use this parameter to ensure that both transducers are being stimulated.
P910 Toggle Relays
Used to energize and de-energize relays directly.
Enter the relay number and then toggle between
energized
and
de-energized
, as
required. Enter 0 to toggle all relays at once.
Applies only to relays with P119 = 0 (algorithm control). Use this parameter to confirm that
relay contacts are opening and closing.
This feature is helpful when P119 does not give expected results even though
programming was verified.
P911 mA Output Value
Access this parameter to display the current value of the mA output.
Additionally, this feature may be used to enter a desired value. The mA output
immediately assumes the value entered regardless of any restrictions programmed.
P912 Transducer Temperature
Use this feature to display the temperature in °C (as monitored by the connected
transducer).
Err is displayed if the transducer is not equipped with an internal temperature sensor.
Primary Index
Global
Values
0 to 6
Related
•
P119 mA Relay Logic Test
Primary Index
mA output
Values
Range: 0.10 to 25.00
Related
•
P200 mA Output Range
•
P201 mA Output Function
Primary Index
Transducer
Values
Range: -50 to 150
Summary of Contents for HydroRanger 200
Page 1: ...Instruction Manual July 2009 200 hydroranger ...
Page 232: ...Page 222 HydroRanger 200 INSTRUCTION MANUAL 7ML19985FC03 mmmmm Parameters Notes ...
Page 264: ...Page 254 HydroRanger 200 INSTRUCTION MANUAL 7ML19985FC03 mmmmm Appendix H Software Rev Notes ...
Page 278: ...Notes ...