HydroRanger 200 - INSTRUCTION MANUAL
Page 87
mm
mmm
Communicat
ions
HydroRanger 200 Communications
HydroRanger 200 Communication Systems
The HydroRanger 200 is an integrated level controller capable of communicating process
information to a Supervisory Control and Data Acquisition (SCADA) system, via a serial
device such as a radio modem, leased line, or dial-up modem.
The HydroRanger 200 supports the following two communication protocols:
Modbus
Modbus is an industry standard protocol used by SCADA and HMI systems. The
HydroRanger 200 uses Modbus to communicate via the RS-485 port. For a description of
the Modbus protocol, contact your local Schneider representative.
Dolphin
Dolphin is a proprietary Siemens Milltronics protocol designed to be used with Dolphin
Plus.
For more information on Dolphin Plus or to obtain a copy of the software, please go to
www.siemens.com/processautomation to contact your Siemens Milltronics
representative.
Note:
Dolphin Plus is only compatible with product software versions 1.06 and
earlier. See P900 for Software Revision Number.
HydroRanger 200
Connection via radio modem, dial-up modem, or leased line modem