Troubleshooting
SITOP UPS1600 / BAT1600 / UPS1100
182
Equipment Manual, 07.2021, A5E37775406-11-76
Error
Type
Ex-
tend-
ed
Error
Type
Severity Alarm Text
Help Text
256
22
MR
Wrong device ID
An attempt was made to update the software with an update
file that is not suitable for the UPS1600.
256
23
MR
Corrupt data record
Error during software update - try to update the software again
256
24
MR
Wrong update
An attempt was made to update the software with an invalid
update file. The update file is probably too old.
256
25
MR
Too much data
An entry in the software update cannot contain more than
32 bytes of reference data.
256
26
F
Device failure
Device failure
256
27
F
No boot loader available
No boot loader available
257
1
MD
Buffer mode is not possible Buffer mode not possible - check cabling, fuse and battery
voltages
257
2
MR
Device temperature critical
(too high)
Device temperature higher than 100 °C. Caution: The highest
permitted temperature could be exceeded!
257
3
MR
Device temperature critical
(too low)
Device temperature less than -10 °C. Device could leave the
operating range.
257
4
MR
High-resistance connection
to battery
High-resistance connection to battery - check battery power
cable
257
5
MD
Power supply to at least one
battery interrupted
Connection to battery interrupted - check connection and fuse
257
6
MR
Unknown battery
Data from the battery cannot be read correctly. Battery is defec-
tive or not supported by SIEMENS.
257
7
MD
Overcurrent
Output current of UPS1600 is too high. Output is switched off
for 20 s. The output is switched on again after 20 s.
257
8
N
Reset buffer timer
PC is shutting down
257
9
N
UPS1600 off
UPS1600 off - buffer time exceeded.
257
10
MR
Output switched off
The UPS1600 output was shut down as result of executing an
instruction or an error situation (e.g. overtemperature, exces-
sive output current).
257
11
N
Output switched on
obsolete from V2.3
The UPS1600 output was switched on again as result of execut-
ing an instruction or the correction of an error situation.
257
12
N
Reset executed
Input voltage at UPS1600 was OK again before the buffer time
expired. Connected devices are reset by switching off the
UPS1600 outputs for the configured time.
257
13
MD
Battery test is negative
A cyclic battery test will be performed
Remark:
For firmware versions from V2.2 - and for versions V2.0.× from
version V2.0.5, the alarm is deactivated.
257
14
N
Software update successful Previous software update was successful - UPS1600 is opera-
tional again.
257
15
MD
Input voltage is too high
Input voltage exceeds 30 V. UPS1600 is not operational.
257
16
MR
Surplus battery
More than 6 batteries are connected. Connect max. of
6 batteries to the Energy Storage Link.
257
17
F
UPS1600 parameters cor-
rupt
UPS1600-parameters corrupt - try to update the software.
257
18
F
Device overtemperature
Output and battery charging is switched off to prevent damage
to the device.
257
19
MR
Capacity test
Capacity test being performed