Description, device design, dimension drawing
2.1 Device description
SITOP UPS1600 / BAT1600 / UPS1100
22
Equipment Manual, 07.2021, A5E37775406-11-76
2.1.2
SITOP BAT1600
The SITOP BAT1600 battery modules consist of a battery holder with two maintenance-free,
sealed lead-gel or one to three LiFePO4 batteries with terminals for the connecting cables to
the SITOP UPS1600 uninterruptible power supply. The SITOP BAT1600 includes a printed-
circuit board for monitoring the battery functions and the communication with the SITOP
UPS1600. A three-color LED indicates the operating status as well as the status of the
communication connection to the SITOP UPS1600. The LED flashes when the batteries are
being replaced or for faults and alarms.
See SITOP BAT1600 (Page 45)
Note
SITOP BAT1600 battery modules can only be used together with SITOP UPS1600 from SW
Version V2.4 and higher.
Up to 6 SITOP BAT1600 of the same type can be connected in parallel with a SITOP UPS1600.
See Chapter Connecting SITOP BAT1600 battery modules to the UPS module (Page 213)
Connecting battery modules in parallel. To replace batteries, see Chapter Battery replacement
SITOP BAT1600 (Page 225). Batteries cannot be replaced for battery modules with LiFePO4
batteries.
Summary of Contents for 6EP4131-0GB00-0AY0
Page 6: ...Overview SITOP UPS1600 BAT1600 UPS1100 6 Equipment Manual 07 2021 A5E37775406 11 76 ...
Page 12: ...Table of contents SITOP UPS1600 BAT1600 UPS1100 12 Equipment Manual 07 2021 A5E37775406 11 76 ...
Page 262: ...Environment SITOP UPS1600 BAT1600 UPS1100 262 Equipment Manual 07 2021 A5E37775406 11 76 ...