Mounting position, mounting clearances
6.3 SITOP UPS1100
SITOP UPS1600 / BAT1600 / UPS1100
208
Equipment Manual, 07.2021, A5E37775406-11-76
6.3
SITOP UPS1100
6.3.1
Standard mounting position
The device is suitable for the direct wall mounting. Devices 6EP4131-0GB00-0AY0 (1.2 Ah),
6EP4132-0GB00-0AY0 (2.5 Ah), 6EP4133-0GB00-0AY0 (3.2 Ah) and 6EP4133-0JB00-0AY0
(5 Ah) can also be snapped onto a TH35×15 DIN rail (EN 60715), and device 6EP4131-0GB00-
0AY0 (1.2 Ah) also onto a TH35×7.5 DIN rail (EN 60715). It should also be mounted at the
coolest point in the control cabinet (e.g. in the lower part of the control cabinet). The device
must be mounted vertically in such a way that the terminals are at the bottom. There should
be a minimum clearance of 15 mm above the device.
No clearance is required at the side.
6.3.2
Other mounting positions
Note
In the case of mounting positions that deviate from the standard mounting position, reduced
mechanical resistance of the devices against vibration and shock must be expected.
Particularly when installing on a vertically fastened standard mounting rail, additional
measures may be required, e.g. to prevent the device from slipping on the rail.
All mounting positions have been released, except the following:
For UPS1100 1.2 Ah: Mounting position (2) (see the following diagram)
all other UPS1100: Mounting position (5) (see the following diagram)
Figure 6-19 Mounting positions forbidden for the UPS1100