Technical data
8.3 Buffer times
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
241
8.3
Buffer times
8.3.1
SITOP BAT1600
Type of
power sup-
ply
6EP4132-
0JA00-0AY0
24 V/2.5 Ah
LiFePO4
6EP4133-
0GA00-0AY0
24 V/3.2 Ah
6EP4134-
0JA00-0AY0
24 V/7.5 Ah
LiFePO4
6EP4135-
0GE00-0AY0
24 V/12 Ah
6EP4137-
0GE00-0AY0
24 V/38 Ah
Load cur-
rent
Buffer times* Buffer times* Buffer times* Buffer times* Buffer times*
1 A
1 h 40 min
2 h 9 min
8 h 30 min
6 h 28 min
30 h
2 A
50 min
1 h 13 min
4 h 20 min
3 h 39 min
16 h 40 min
3 A
30 min
51 min
2 h 40 min
2 h 33 min
11 h 20 min
4 A
20 min
39 minutes
1 h 50 min
1 h 57 min
8 h
6 A
10 min
27 minutes
1 h 20 min
1 h 20 min
5 h
8 A
6 min
20 min
50 min
61 min
3 h 40 min
10 A
4 minutes
16 min
40 min
49 min
2 h 50 min
12 A
2 minutes
14 min
30 min
41 minutes
2 h 00 min
14 A
1 minute
12 minutes
25 min
35 min
1 h 50 min
16 A
< 1 min
-
20 min
31 min
1 h 40 min
20 A
-
-
15 minutes
25 min
1 h 15 min
30 A
-
-
6 min
17 minutes
45 min
40 A
-
-
3 min
13 min
30 min
* When determining buffer times, the discharge duration of new and completely charged
battery modules at a battery temperature of 25 °C down to shutdown of the DC UPS (min.
20 V) was used as basis. Buffer times for additional values can be determined using the SITOP
Selection Tool: TIA Selection Tool (