Environmental conditions
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
259
6EP4131-0GB00-0AY0
(1.2 Ah)
6EP4133-0GB00-0AY0
(3.2 Ah)
6EP4134-0GB00-0AY0
(7 Ah)
6EP4135-0GB00-0AY0
(12 Ah)
6EP4132-0GB00-0AY0
(2.5 Ah)
6EP4133-0JB00-0AY0
(5 Ah)
Ambient temperature
0 ... 40 °C for natural convec-
tion
(self convection)
1.2 / 3.2 / 7 Ah: From product
version 3: -15 ... 50 °C for
natural convection
(self convection)
12 Ah: From product ver-
sion 2: -15 ... 50 °C for natu-
ral convection
(self convection)
-20 ... 60 °C for natural con-
vection
(self convection)
-20 ... 50 °C for natural con-
vection
(self convection)
Tested according to:
•
EN 60068-2-1 Cold
•
EN 60068-2-2 Dry heat
•
EN 60068-2-78 Humid heat, constant
•
EN 60068-2-14 Temperature change
Remark: The service life of the UPS1100 battery modules
(decrease to 50 % of the original capacity) depends on the
battery temperature, at approximately 20 °C: 4 years, 30 °C:
2 years, 40 °C: 1 year
Transport and storage tem-
perature
-20 ... 50 °C
-40 ... 60 °C
-40 ... 60 °C
Tests (packed for shipping) according to:
•
EN 60068-2-1 Cold
•
EN 60068-2-2 Dry heat
•
EN 60068-2-30 Humid heat, cyclic
Humidity class
Climatic class 3K3 according to EN 60721, 5 - 95 % no con-
densation
Degree of pollution
2
Mechanical stress in opera-
tion
Tested according to:
•
EN 60068-2-6 vibration, test Fc:
3.5 mm deflection in the range 5 - 9 Hz
1 g acceleration in the range 9 - 150 Hz
•
EN 60068-2-27 shock, test Ea:
acceleration 150 m/s
2
, test duration 11 ms