Engineering and remote access
3.9 Web server
SITOP UPS1600 / BAT1600 / UPS1100
140
Equipment Manual, 07.2021, A5E37775406-11-76
3.9.6.4
Online functions
From firmware release V2.3.0, the output of the SITOP UPS1600 can be switched on and
switched off via the WEB interface.
Switching off the output is not retentive, and is deactivated when the SITOP UPS1600
restarts. This function initiates an alarm "Output switched off" and has alarm ID "257/10".
Firmware update
The firmware update process is described in detail in the "Firmware update readme", which is
provided with the firmware update download package.
Follow the instructions provided there carefully. The files for updating the firmware are
available online at: (
https://support.industry.siemens.com/cs/ww/en/view/79207181
Refer also to Section Firmware update with web server (Page 135).
Summary of Contents for 6EP4131-0GB00-0AY0
Page 6: ...Overview SITOP UPS1600 BAT1600 UPS1100 6 Equipment Manual 07 2021 A5E37775406 11 76 ...
Page 12: ...Table of contents SITOP UPS1600 BAT1600 UPS1100 12 Equipment Manual 07 2021 A5E37775406 11 76 ...
Page 262: ...Environment SITOP UPS1600 BAT1600 UPS1100 262 Equipment Manual 07 2021 A5E37775406 11 76 ...