Technical data
8.5 Protection and monitoring
SITOP UPS1600 / BAT1600 / UPS1100
244
Equipment Manual, 07.2021, A5E37775406-11-76
8.5
Protection and monitoring
6EP4134-3AB00- … (10 A)
6EP4136-3AB00- … (20 A)
6EP4137-3AB00- … (40 A)
Current limitation
Typ.
•
Remark
30 A
Power boost with 300 % I
out rated
for typ. 30 ms
60 A
Power boost with 300 % I
out rated
for typ. 30 ms
120 A
Power boost with 300 % I
out rated
for typ. 30 ms
Short-circuit protec-
tion
Shutdown after 30 ms
Reverse polarity pro-
tection
With respect to the input voltage U
in
and with respect to batteries
Overload/short-circuit
indicator
Yes, restart in normal operation
6EP4131-
0GB00-0AY0
(1.2 Ah)
6EP4132-
0GB00-0AY0
(2.5 Ah)
6EP4133-
0GB00-0AY0
(3.2 Ah)
6EP4133-
0JB00-0AY0
(5 Ah)
6EP4134-
0GB00-0AY0
(7 Ah)
6EP4135-
0GB00-0AY0
(12 Ah)
Short-circuit
protection
Yes, fuse
Reverse polarity
protection
Yes
6EP4132-
0JA00-0AY0
(2.5 Ah)
6EP4133-
0GA00-0AY0
(3.2 Ah)
6EP4134-
0JA00-0AY0
(7.5 Ah)
6EP4135-
0GE00-0AY0
(12 Ah)
6EP4137-
0GE00-0AY0
(38 Ah)
Short-circuit
protection
Yes, fuse
Reverse polarity
protection
Yes