Environmental conditions
SITOP UPS1600 / BAT1600 / UPS1100
258
Equipment Manual, 07.2021, A5E37775406-11-76
6EP4132-0JA00-0AY0
(2.5 Ah)
6EP4134-0JA00-0AY0
(7.5 Ah)
6EP4133-0GA00-0AY0
(3.2 Ah)
6EP4135-0GE00-0AY0
(12 Ah)
6EP4137-0GE00-0AY0
(38 Ah)
Ambient temperature
-20 ... 60 °C for natural con-
vection
(self convection)
-15 … 50 °C for natural convection
(self convection)
Tested according to:
•
EN 60068-2-1 Cold
•
EN 60068-2-2 Dry heat
•
EN 60068-2-78 Humid heat, constant
•
EN 60068-2-14 Temperature change
Remark: The service life of the SITOP BAT1600 battery modules (decreases to 80 % of the
original capacity) depends on the battery temperature. For a temperature increase of 10 °C,
referred to 20 °C, the service life is halved
Transport and storage tem-
perature
-20 … 35 °C (transport -30 …
70 °C)
-20 ... 50 °C
Tests (packed for shipping) according to:
•
EN 60068-2-1 Cold
•
EN 60068-2-2 Dry heat
•
EN 60068-2-30 Humid heat, cyclic
Humidity class
Climatic class 3K3 acc. to EN 60721, 5 - 85 % without condensation
Degree of pollution
2
Mechanical stress in opera-
tion
Tested according to:
•
EN 60068-2-6 vibration, test Fc:
3.5 mm deflection in the range 5 - 9 Hz
1 g acceleration in the range 9 - 150 Hz
•
EN 60068-2-27 shock, test Ea:
acceleration 150 m/s
2
, test duration 11 ms
Damaging gases
Tested according to:
•
EN 60068-2-42 sulfur dioxide
•
EN 60068-2-43 hydrogen sulfide
Atmospheric pressure
Operation:
•
1080 - 795 hPa (-1000 - 2000 m)
•
Operation at altitudes exceeding 2000 m above sea level is not permissible.
Storage:
•
1080 - 660 hPa (-1000 - 3500 m)
Summary of Contents for 6EP4131-0GB00-0AY0