Description, device design, dimension drawing
2.3 Operator controls
SITOP UPS1600 / BAT1600 / UPS1100
34
Equipment Manual, 07.2021, A5E37775406-11-76
2.3
Operator controls
2.3.1
SITOP UPS1600
2.3.1.1
Rotary coding switch, switch-in threshold
The switch-in threshold can be set using the rotary coding switch
⑦
on the device front
between 21.0 V and 25.0 V (21 - 21.5 - 22 - 22.5 - 23 - 24 - 25 volt). The delivery state is
21.5 V
For devices with an interface (…-1AY0, …-2AY0), the coding switch has an additional position
REN. If this is selected, the software settings (for the switch-in threshold and the backup
time) apply rather than the hardware settings. In the switch position REN, connection X2.13
(INTERRUPT - reset after buffer mode) of the signal terminal (see Chapter Signal terminal
(Page 28)) has no effect.
Figure 2-16 Rotary coding switch, switch-in threshold
Note
It is only permissible to operate the rotary coding switch using an insulated screwdriver.
The stop buffering voltage is a voltage to be set, which must not be fallen below in the case
of a buffering event. This ensures that the undervoltage monitoring of the device supplied
from the UPS does not trip as a result of the decreasing output voltage during the buffering
event. Customers can set the voltage.
For notes on actuating the rotary coding switch (screwdriver, torque), see Figure 2-5