Engineering and remote access
3.10 OPC UA server
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
179
3.10.6.26
Additional parameters
These nodes are listed at the first level in the object tree
Display name
Data type
Definition
Description
DeviceManual
String
PropertyType
Address (path in the file system or URL / web address) of the
operating instructions for the device.
Hardware Revision
String
PropertyType
Revision status of the device hardware.
Manufacturer
LocalizedText
PropertyType
Name of the company that manufactured the device.
Model
LocalizedText
PropertyType
Model
ModuleIdentNumber
UInt32
PropertyType
Module identification number
OrderNumber
String[20]
PropertyType
Article number
RevisionCounter
Int32
PropertyType
Incremental counter that specifies how often the static data
in the device was modified.
SerialNumber
String
PropertyType
ID, which uniquely identifies the device for the device manu-
facturer.
SoftwareRevision
String
PropertyType
Revision status of the device software.
3.10.7
OPC UA performance
OPC UA provides the option of collectively transferring modified actual values in the form of a
subscription. The minimum pole interval of such a subscription is 100 ms. A maximum of
150 data nodes can be simultaneously monitored, independent of whether these data nodes
are assigned one or various subscriptions.
OPC UA does not support any type of realtime communication, neither for actual values (read
data) nor for setpoints (written data). As a consequence, it is not possible to specify an
update/refresh rate or a maximum data flow rate.
3.10.8
Recommissioning after a basic device has been replaced - or after restoring
the factory settings
If, for service reasons it is necessary to replace the basic unit - or store the factory settings,
then please observe the following notes:
1.
Brand new basic units or basic units, where the factory settings have been restored, have no
IP address. However, this is generally necessary so that the device can be accessed using
OPC UA. Proceed as described in Chapter "General (Page 142)", Section "Communication
interface" to assign the device a certain IP address.
2.
The configuration must be loaded to the device. This can be done in the following ways:
•
Proceed as described in Chapter "Load / Save (Page 155)" to load a valid configuration into
the device (previously saved via web server).
•
Load a valid configuration to the device via OPC UA. Ensure that the necessary user
account is available in the device for access via OPC UA. The latter can be created using a
web server, see Chapter "Web server (Page 144)".
Summary of Contents for 6EP4131-0GB00-0AY0
Page 6: ...Overview SITOP UPS1600 BAT1600 UPS1100 6 Equipment Manual 07 2021 A5E37775406 11 76 ...
Page 12: ...Table of contents SITOP UPS1600 BAT1600 UPS1100 12 Equipment Manual 07 2021 A5E37775406 11 76 ...
Page 262: ...Environment SITOP UPS1600 BAT1600 UPS1100 262 Equipment Manual 07 2021 A5E37775406 11 76 ...