7.4 Connecting SITOP UPS1100 battery modules to the UPS module
SITOP UPS1600 / BAT1600 / UPS1100
218
Equipment Manual, 07.2021, A5E37775406-11-76
①
DC input X1
②
Signal terminal X2
③
Fuses F1/F2 (F2 only for 7/12 Ah)
④
Signaling (LED)
⑤
Reset button
⑥
Screw to replace the battery (Torx T10)
Connecting a SITOP UPS1100 battery module
1.
Connect the SITOP UPS1600 with the battery module at power terminal
①
and at signal
terminal
②
.
2.
Insert the fuse
③
.
The connected battery module is automatically detected.
Note
Please note that identifying a SITOP UPS1100 battery module at a SITOP UPS1600 after
inserting the connecting cables or after inserting the fuse in the SITOP UPS1100 battery
module can typically take 20 seconds, but up to 2 minutes.
Connecting several SITOP UPS1100 battery modules
WARNING
In hazardous zones (ex-applications), it is absolutely prohibited that SITOP UPS1100 battery
modules are connected in parallel.
To extend the power failure buffering time, up to 6 identical SITOP UPS1100 battery modules
can be connected to a SITOP UPS1600.