Engineering and remote access
3.4 SIMATIC STEP 7 in the TIA Portal
SITOP UPS1600 / BAT1600 / UPS1100
68
Equipment Manual, 07.2021, A5E37775406-11-76
3.4.6
Assigning SITOP BAT1600 / UPS1100 battery modules to the basic unit SITOP
UPS1600
The basic functions of the uninterruptible power supply are available with all of the battery
modules that are compatible with the SITOP UPS1600. The SITOP UPS1100 5 Ah LiFePO4
battery is only supported by SITOP UPS1600 from software version V2.1; all SITOP BAT1600
battery modules first from software version V2.4.
Additional functions are available with battery module SITOP BAT1600 or SITOP UPS1100:
•
Automatic detection of the battery module rated values
•
Automatic management of up to six battery modules
•
Temperature-controlled charging
•
Charge status display
•
Battery status (battery health) status display for SITOP BAT1600
•
Diagnostics using the SITOP Manager and the web server
Using an example, in the following steps you are shown how the SITOP UPS1600 is assigned
a battery module.
Note
Only SITOP BAT1600 or SITOP UPS1100 battery modules of the same type can be added to
the slots of a SITOP UPS1600.
The number of battery modules that can be configured is limited to six. The description is
only applicable to devices that were linked to via the HSP.
Preconditions
•
STEP 7 in the TIA Portal has been opened and a project has been created.
•
A SITOP UPS1600 has been integrated in the project.
Procedure
The procedure is only applicable for devices integrated using HSP.
1.
In the device view, select the SITOP UPS1600 basic unit.
2.
In the Hardware catalog , navigate to the SITOP BAT1600/UPS1100 battery modules under
"Power supply and distribution\Power supplies\SITOP UPS\UPS1100".
3.
Select the required battery module in the hardware catalog.
In the "Information" area you can see information about the expansion module, and when
necessary you can change the preselected (default) version.