Engineering and remote access
3.9 Web server
SITOP UPS1600 / BAT1600 / UPS1100
150
Equipment Manual, 07.2021, A5E37775406-11-76
Basic unit
Buffering
Parameter
Value range
Default setting
Connection threshold
21 - 25 V
22.5 V
Buffer time
1 - 32767 s
600 s
Maximum buffer time
1)
Yes / No
No
Discharge cut-off voltage at 20 °C
18 - 23 V
18.5 V (for LiFePO4 battery 20.5 V)
Additional buffer time after the PC was powered down.
3)
1 - 300 s
60 s
Expected buffer current
1)
0 - 40 A
0 A
Reset time:
1 - 120 s
5 s
Buffering allowed
Yes / No
Yes
Enable reset after buffering
Yes / No
No
1)
Parameter only available from SW version V2.0 and higher
2)
Parameter only available from SW version V2.1 and higher
3)
Valid from V2.0.4 or V2.1