Engineering and remote access
3.6 Cyclic and acyclic data
SITOP UPS1600 / BAT1600 / UPS1100
122
Equipment Manual, 07.2021, A5E37775406-11-76
Data
Description
Data type
LED state
LED states
Unsigned8
Fill byte(s)
-
2 x Unsigned8
SWD
SW revision
Unsigned32
Battery MID
Battery Module Ident Number
Unsigned32
0x0020: State information (reading)
Data
Description
Data type
Remaining buffer time [1 s]
Probable remaining buffer time. The remaining buffer time is cal-
culated based on the present battery charge and the average cur-
rent over a 10 minute period.
Unsigned32
Total operating time [1 h]
Total operating time.
Unsigned32
Total calculated battery capacity
[0.1 Ah]
Total calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Unsigned16
Calculated battery 1 capacity
[0.1 Ah]
Battery 1: Calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Unsigned16
Calculated battery 2 capacity
[0.1 Ah]
Battery 2: Calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Unsigned16
Calculated battery 3 capacity
[0.1 Ah]
Battery 3: Calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Unsigned16
Calculated battery 4 capacity
[0.1 Ah]
Battery 4: Calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Unsigned16
Calculated battery 5 capacity
[0.1 Ah]
Battery 5: Calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Unsigned16
Calculated battery 6 capacity
[0.1 Ah]
Battery 6: Calculated battery capacity
For < V2.3.x, the variable is not supported and supplies value 0.
Unsigned16
Input voltage [0.01 V]
Input voltage: Measured rms value of the supply voltage at the
input of the SITOP UPS1600.
Unsigned16
Input current [5 mA]
Current measured at the input of the SITOP UPS1600.
Unsigned16
Output voltage [0.01 V]
Voltage measured at the output of the SITOP UPS1600.
Unsigned16
Load current [5 mA]
Load current measured at the output of the SITOP UPS1600.
Unsigned16
Measured charge current [1 mA]
Measured battery charge current of the SITOP UPS1600.
Unsigned16
Battery voltage [0.01 V]
Measured battery voltage of the connected battery modules
Unsigned16
Output current [5 mA]
Load current measured at the output of the SITOP UPS1600.
Unsigned16
Charge voltage [0.01 V]
Voltage used to charge the battery during the constant-current
charging phase
Unsigned16
Fill byte(s)
-
3 x Unsigned8
Valid configuration
Valid configuration: Indicates whether the software parameters or
the parameters at the rotary coding switch are used. The corre-
sponding setting should be made at the rotary coding switch for
the buffer threshold.
Unsigned8
Number of batteries
Number of connected battery modules. Here, only SITOP BAT1600
or SITOP UPS1100 battery modules (SITOP system batteries) are
counted.
Unsigned8
Fill byte(s)
-
7 x Unsigned8
Battery 1 change recommended
Battery 1: Battery replacement recommended: The battery capacity
is not sufficient for the defined buffer time.
Unsigned8
Battery 2 change recommended
Battery 2: Battery replacement recommended: The battery capacity
is not sufficient for the defined buffer time.