Engineering and remote access
3.10 OPC UA server
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
169
Display name
Data type
Definition
Description
AlarmBatteryDischarge
BecauseChargingDeac-
tivated
Boolean
PropertyType
Low charge status of the battery as a result of deactivated
charging function.
AlarmBatterySOHtest
CanceledBuffering
Boolean
PropertyType
Capacity test canceled. Buffering was started.
AlarmBatterySOHtest
CanceledByConfigura-
tion
Boolean
PropertyType
Capacity test canceled due to changed or invalid configura-
tion
AlarmBatterySOHtest
CanceledByUser
Boolean
PropertyType
User canceled the capacity test.
AlarmBatterySOHtest
CanceledInputVolt-
ageHigh
Boolean
PropertyType
Capacity test canceled. Input voltage is too high
AlarmBatterySOHtest
CanceledInsufficient-
Load
Boolean
PropertyType
The capacity test was canceled due to an insufficient system
load.
AlarmBatterySOHtest
CanceledNotFull
Boolean
PropertyType
Capacity test canceled. Batteries are not fully charged.
AlarmBatterySOHtest
Running
Boolean
PropertyType
Capacity test being performed.
AlarmBatterySOHtest
Running
Boolean
PropertyType
Battery 'State of Health' tests (SoH) are in progress.
AlarmBufferMode
NotPossible
Boolean
PropertyType
Buffer mode not possible - check settings, cabling, fuse, and
battery voltages
AlarmBuffer
TimerReset
Boolean
PropertyType
PC is shutting down
AlarmBuffering
Boolean
PropertyType
Device is in buffer mode.
AlarmChargeCurrent
ManualChanged
Boolean
PropertyType
Max. permissible charging current was limited as a result of
the configuration parameters
AlarmCommunication
ToDeviceFailed
Boolean
PropertyType
PROFINET connection available - SITOP UPS1600 is defective
AlarmDevice
Failure
Boolean
PropertyType
Device failure
AlarmDevice
Overtemperature
Boolean
PropertyType
Output and battery charging is switched off to prevent dam-
age to the device.
AlarmDevice
ParameterCorrupt
Boolean
PropertyType
SITOP UPS1600 parameters corrupt - try to update the soft-
ware.
AlarmDevice
PoweredUp
Boolean
PropertyType
Device powered up
AlarmDevice
TemperatureHigh
Boolean
PropertyType
Device temperature higher than 100° C. Caution: The high-
est permitted temperature could be exceeded!
AlarmDevice
TemperatureLow
Boolean
PropertyType
Device temperature lower than -10° C. Device could leave
the operating range.
AlarmDevice
TurnedOff
Boolean
PropertyType
SITOP UPS1600 off - buffer time exceeded or PC was shut
down
AlarmFirmware
UpdateOK
Boolean
PropertyType
Previous software update was successful - SITOP UPS1600 is
operational again.
AlarmFuseBroken
Boolean
PropertyType
Fuse is defective.
AlarmInput
VoltageHigh
Boolean
PropertyType
Input voltage exceeds 30 V. SITOP UPS1600 is not opera-
tional.
AlarmInsufficient-
Charge
Boolean
PropertyType
The configured buffer time may not be reached at this time
due to the low battery charge.