SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
211
Installation
7
Note
When installing the devices, the relevant country-specific regulations must be complied with.
The 24 V supply voltage must comply with SELV (ES1) in accordance with EN62368-1 and
EN50178.
Only qualified personnel are allowed to install the device/system and set it into operation.
It is not permissible that the connections are attached or detached in operation.
Note
for SITOP BAT1600 and SITOP UPS1100
It is recommended that the batteries are only stored fully charged.
The lead acid batteries are fully charged when the device is delivered.
The LiFePO4 battery SITOP UPS1100 (5 Ah) is only supplied, charged up to a maximum of
30 % of the rated charge (to comply with transport regulations).
For air freight, the LiFePO4 battery of the SITOP UPS1600 battery module (2.5 Ah and 7.5 Ah)
is only charged up to maximum of 30 %; for other transport types, up to 100 %.
The self-discharge rate of the batteries is approx. 3%/month for a temperature of 20° C. This
value is temperature dependent and becomes more unfavorable for an increasing
temperature, and more favorable for a decreasing temperature.
The fuse should only be inserted in the fuse holder when commissioning the device.
When storing SITOP BAT1600 / SITOP UPS1100 battery modules in completely wired/cable
systems (with SITOP UPS1600 and fuse inserted in the SITOP BAT1600 / SITOP UPS1100) it
should be noted that an additional discharge current (leakage current) flows.
SITOP BAT1600 2.5 Ah is only recommended in conjunction with SITOP UPS1600 10 A.
SITOP BAT1600 3.2 Ah is only recommended in conjunction with SITOP UPS1600 20 A or less.
SITOP BAT1600 7.5 Ah, 12 Ah, 38 Ah is only recommended in conjunction with SITOP
UPS1600 40 A or less.
SITOP UPS1100 1.2 Ah is only recommended in conjunction with SITOP UPS1600 10 A.
SITOP UPS1100 2.5 Ah, 3.2 Ah and 5 Ah are only recommended in conjunction with SITOP
UPS1600 10 A and 20 A.
When using battery modules without Energy Storage Link, it must be ensured that the
selected batteries match the data of the SITOP UPS1600 (static and dynamic load current,
charge current).