Engineering and remote access
3.4 SIMATIC STEP 7 in the TIA Portal
SITOP UPS1600 / BAT1600 / UPS1100
84
Equipment Manual, 07.2021, A5E37775406-11-76
3.4.10
Firmware update
WARNING
The SITOP UPS1600 is reset while updating the firmware. For safety reasons, the
output is switched off.
Ensure that no damage is caused to the plant or system.
Ensure that the PG/PC and/or all switches, routers and gateways that are used have an
independent power supply during the firmware update.
WARNING
Firmware update to V2.3.0 with UPS Manager
If the UPS Manager was used to update the firmware to V2.3.0 for devices with PROFINET
interface, then the update cannot be successfully completed. In a case such as this, the
device signals a software error using LED 1 (O.K./BAT.). Such a device can be made
operational again by performing an update using the web server, see Firmware update with
web server (Page 135).
Note
Install the current version of the SITOP Managers, before you start the firmware update. The
installation file for the SITOP Manager is available at no charge on the SITOP home page
) or directly
https://support.industry.siemens.com/cs/ww/en/view/109760607
).
Note
Do not switch-off the devices during the firmware update.
The files for updating the firmware (firmware updates) are available online under
http://support.automation.siemens.com/WW/view/en/79207181
). Different firmware
updates are offered depending on the amp rating of the SITOP UPS1600.
Note
Observe the compatibility of the firmware!
Other firmware updates are not compatible.
Determine the amp rating of your SITOP UPS1600 and download the appropriate firmware
update.
Note
From device firmware 2.3, a downgrade can be made to version 2.2.3. A downgrade is not
supported for older versions. Information on how to read out the firmware release from the
device is provided in Section Diagnostics (Page 82).
Summary of Contents for 6EP4131-0GB00-0AY0
Page 6: ...Overview SITOP UPS1600 BAT1600 UPS1100 6 Equipment Manual 07 2021 A5E37775406 11 76 ...
Page 12: ...Table of contents SITOP UPS1600 BAT1600 UPS1100 12 Equipment Manual 07 2021 A5E37775406 11 76 ...
Page 262: ...Environment SITOP UPS1600 BAT1600 UPS1100 262 Equipment Manual 07 2021 A5E37775406 11 76 ...