Description, device design, dimension drawing
2.4 Operating displays and signaling
SITOP UPS1600 / BAT1600 / UPS1100
Equipment Manual, 07.2021, A5E37775406-11-76
41
States of the LEDs
LED 1 (O.K./BAT.)
Signaling
6EP4134-3AB00-…
6EP4136-3AB00-…
6EP4137-3AB00-…
Off
DC-UPS off
Red
DC-UPS defect (severe hardware fault)
Flashing red
(0.25/0.25)
Firmware update
Flashing red (1/1) Software corrupted
Flashing yellow
(0.25/0.25)
Critical temperature identified, overtemperature or overvoltage at the input
Flashing yellow
(1/1)
Buffer mode, output off
Yellow
Buffer mode, output on
Flashing green
(1/1)
DC-UPS OK, output off
Green
DC-UPS OK, output on
LED 2 (BAT.> 85%)
Signaling
6EP4134-3AB00-…
6EP4136-3AB00-…
6EP4137-3AB00-…
Off
Battery module charge state < 10 %
Flashing green
(0.25/0.25)
10 % < battery module charge state < 85 % or firmware update
Flashing green
(1/1)
85 % < battery module charge state < 100 %
Green
Battery module charge state = 100 %
The LED and the relay contact (see Chapter Relay outputs (Page 44)) have two meanings:
1.
If no additional settings have been made, then the previous LED signaling applies.
2.
If an expected buffer current and a buffer time are set under the hardware configuration,
then the LEDs and the relay contact serve as an indicator when buffering is possible with the
two parameters – or is no longer possible.
Note
From the instant in time when the SITOP UPS1600 is switched over into the buffer mode, for
the evaluation, instead of the expected buffer current, the actually measured buffer current is
used. As a consequence, the status of the LEDs and the relay can also change.
Summary of Contents for 6EP4131-0GB00-0AY0
Page 6: ...Overview SITOP UPS1600 BAT1600 UPS1100 6 Equipment Manual 07 2021 A5E37775406 11 76 ...
Page 12: ...Table of contents SITOP UPS1600 BAT1600 UPS1100 12 Equipment Manual 07 2021 A5E37775406 11 76 ...
Page 262: ...Environment SITOP UPS1600 BAT1600 UPS1100 262 Equipment Manual 07 2021 A5E37775406 11 76 ...