Description, device design, dimension drawing
2.4 Operating displays and signaling
SITOP UPS1600 / BAT1600 / UPS1100
42
Equipment Manual, 07.2021, A5E37775406-11-76
LED 3 (ALARM)
Signaling
6EP4134-3AB00-…
6EP4136-3AB00-…
6EP4137-3AB00-…
Red
Output off for 45 seconds because of overcurrent, overtemperature or buff-
er mode not possible
Off
Buffer mode possible
LED 4 (BAT.STATUS)
For several battery modules connected in parallel, the LED only shows the LED status with the
highest priority.
If a SITOP BAT1600 is connected:
Signaling
6EP4134-3AB00-…
6EP4136-3AB00-…
6EP4137-3AB00-…
Off
Module runs up, DC-UPS defective (critical hardware fault)
Flashing green
(0.25/0.25)
Battery is being replaced (button pressed, reset service life)
Flashing green
(1/1)
Battery successfully replaced (LED flashes for 5 s)
Flashing green
(1/1)
Battery replacement recommended (SoH ≤ 20
%)
Green
Battery module OK
Flashing yellow
(0.25/0.25)
End of the battery service life reached (SoH = 0 %) or battery test negative
→ battery must be replaced, buffer mode possible
Flashing yellow
(1/1)
Temperature outside the valid range, communication cable interrupted or
different battery types being used → restricted charge operation
Yellow
Selected buffer time cannot be attained
Flashing red (1/1) Battery replacement canceled (LED flashes for 5 s)
Red
Fuse ruptured/not inserted, power cable interrupted, 1 battery in the mod-
ule is not connected, battery pack voltage is not symmetrical or reset button
is pressed > 2 s
If only SITOP UPS1100 are connected:
As soon as a SITOP BAT1600 is connected, the status of SITOP BAT1600 is displayed, and
married up with the information of SITOP UPS1100.
Summary of Contents for 6EP4131-0GB00-0AY0
Page 6: ...Overview SITOP UPS1600 BAT1600 UPS1100 6 Equipment Manual 07 2021 A5E37775406 11 76 ...
Page 12: ...Table of contents SITOP UPS1600 BAT1600 UPS1100 12 Equipment Manual 07 2021 A5E37775406 11 76 ...
Page 262: ...Environment SITOP UPS1600 BAT1600 UPS1100 262 Equipment Manual 07 2021 A5E37775406 11 76 ...