0x0042: OPC UA server (reading/writing)
Data
Description
Data type
OPCServerEnabled
Activate/deactivate the OPC UA interface of the SITOP UPS1600:
•
0: disable
•
255: enable
Unsigned8
OPCUnencrypdedAccessEnable
Activate/deactivate unencrypted access via the OPC UA interface of
the SITOP UPS1600:
•
0: disable
•
255: enable
Unsigned8
OPCBasic128AccessEnabled
Activate/deactivate encrypted and signed access with Basic 128 via
the OPC UA interface of the SITOP UPS1600:
•
0: disable
•
255: enable
Unsigned8
OPCBasic256AccessEnabled
Activate/deactivate encrypted and signed access with Basic 256 via
the OPC UA interface of the SITOP UPS1600:
•
0: disable
•
255: enable
Unsigned8
OPCBasic256SHA256AccessEnabled Activate/deactivate encrypted and signed access with Basic 256
and SHA 256 via the OPC UA interface of the SITOP UPS1600:
•
0: disable
•
255: enable
Unsigned8
OPCPort
Set port for OPC UA interface (1 to 65535)
Unsigned16
Fill byte(s)
-
1 x Unsigned8
0x0043: NTP client parameters (reading/writing)
Data
Description
Data type
NTPServerEnabled
Activate/deactivate NTP server:
•
0: disable
•
255: enable
Unsigned8 from
V2.2
Fill byte(s)
-
Unsigned8 from
V2.2
NTPServer1
IP address of NTP server 1
VisibleString(16)
from V2.2
NTPServer2
IP address of NTP server 2
VisibleString(16)
from V2.2
NTPServer3
IP address of NTP server 3
VisibleString(16)
from V2.2
NTPServer4
IP address of NTP server 4
VisibleString(16)
from V2.2