Engineering and remote access
3.9 Web server
SITOP UPS1600 / BAT1600 / UPS1100
144
Equipment Manual, 07.2021, A5E37775406-11-76
Web server
Here, you can make general settings and define which actions should be automatically
executed.
Parameter
Value range
Default setting
Activate web server on this module
Yes/no
No
Permit access only with HTTPS
Yes/no
Yes
Log off automatically after 15 minutes Yes/no
No
Update interval
0 / 5 s / 10 s / 20 s / 30 s / 60 s
0 = no automatic update
•
Activate web server on this module
Define whether it is permissible that this device is accessed via the web server.
•
Permit access only with HTTPS
Define whether access is only permissible via HTTPS.
•
Download certificate
By pressing button "Download certificate", you can download the certificate for an
encrypted connection via HTTPS.
•
Log off automatically after 15 minutes
Define whether a user should be automatically logged off after closing the web server.
•
Update interval
Define the intervals in which the actual values are sent to the web server.