BF362-5
24 V 5 A EN54-4 Boxed PSU
Installation Instructions
VdS
G209197
FIRE ALARM
ancillaries
1 of 2
Approved Document No. DFU0003611 Rev 5
THIS EQUIPMENT MUST ONLY BE INSTALLED AND MAINTAINED BY A SUITABLY SKILLED AND TECHNICALLY
COMPETENT PERSON. THE PSU
S
ARE CLASS 1 EQUIPMENT AND MUST BE EARTHED.
BF362-5 is a boxed Mains to regulated DC power supply providing 5 A @ 24 Vdc. Combining the functions of a power
supply unit, battery charging unit and battery monitoring unit, it is fully compliant with the current edition of
EN 54-4:1997 + A1:2003 + A2:2007.
INSTALLATION
Location
The power supply must be sited indoors on a dry, flat surface in an area that is well ventilated. Ideally the panel
indicators should be at eye level and the ambient light level should allow the status of the indicators to be clearly seen.
Mounting
Using the five mounting holes provided, mount the metal base securely onto a wall. Assess the condition and
construction of the wall and use suitable screw fixings. The mounting holes are suitable for use with No.8-10 or
4-5 mm countersunk screws. Any dust or swarf created during the mounting process must be kept out of the enclosure
and care must be taken not to damage any wiring or components.
Wiring and Cable Entry
All wiring should be installed in accordance with the current edition of the IEE Wiring Regs
(BS 7671), or the relevant national standards. The requirement for the Mains supply to the
panel is fixed wiring, using 3-core cable (no less than 1 mm
2
and no greater than 2.5 mm
2
),
or a suitable three conductor system fed from an isolating switched spur fused at 3 A.
In order to maintain cable segregation the incoming Mains cable should be fed into the
panel via the top centre knockouts (provided on the metal base). Knockouts should be
removed with a sharp, light tap using a flat 6 mm broadsided screwdriver, as shown in the
diagram (see right). Always ensure that if a knockout is removed, the hole is filled with a
good quality 20 mm cable gland. Any unused knockouts must be securely blanked off.
WARNING: DO NOT ATTEMPT TO CONNECT THE MAINS SUPPLY TO THE POWER
SUPPLY PCB UNLESS ALL COMPONENTS ARE SECURELY INSTALLED IN THE ENCLOSURE.
Terminate the Mains cable at the Power Supply connector block CONN1 (see Figure 1 below).
RPF0361000 Rev2
Temp
Display
Black- Red+
BATTERY
FUSE
F2
F5A
CONN4
0V Charge
Off
C NC NO
Fault Relay
No Batteries
PLK1
PLK2
Fit for 5.5 to 18Ahr
Not fitted for 1.6 to 5.5Ahr
PL2
RLY1
CONN3
Output
C10
C10
+
+
+
+
CONN5
0V
+V
VR1
DO NOT
ADJUST
C6
C6
PL1
PL3
T2AH 250V
HRC
PRIMARY
FUSE F1
LED MUST
EXTINGUISH
BEFORE
SERVICE
C1
TX1
C11
C11
D7
D7
R24
R24
Battery
C24
C24
C20
C20
C23
C23
C31
C31
Mains Input Terminals (CONN1)
L = Live, N = Neutral, = Earth
CLASS 1 EQUIPMENT MUST BE EARTHED.
Connect incoming Mains earth wire
to the earth terminal and NOT to the
base earth post.
PSU Earth Strap
DO NOT operate this equipment
without connecting this strap to the
base earth post.
Display Connector (PL1)
High Temp. Output (PL2)
Charge Off Input (CONN4)
Incoming Mains Cable
Must be segregated from other
cables and only enter the panel
through the top central knockouts.
Hazardous Voltages Present LED
When lit red, hazardous voltages
are present on the components
and copper in the hashed area of
the PCB.
DO NOT TOUCH!
Supply Output (CONN5)
Battery Input (CONN5)
Figure 1 - Power Supply PCB Layout and Connection Details
Battery Charge Current Link (PLK2)
Fault Relay (CONN3)
Battery Monitoring Link (PLK1)
If batteries NOT used, fit PLK1 link.
See Technical Specification
overleaf for further details
0786-CPD-20892