BF362-5

24 V 5 A EN54-4 Boxed PSU

Installation Instructions

VdS

G209197

FIRE ALARM

ancillaries

1 of 2

Approved Document No. DFU0003611 Rev 5

THIS EQUIPMENT MUST ONLY BE INSTALLED AND MAINTAINED BY A SUITABLY SKILLED AND TECHNICALLY
COMPETENT PERSON. THE PSU

S

ARE CLASS 1 EQUIPMENT AND MUST BE EARTHED.

BF362-5 is a boxed Mains to regulated DC power supply providing 5 A @ 24 Vdc. Combining the functions of a power
supply unit, battery charging unit and battery monitoring unit, it is fully compliant with the current edition of
EN 54-4:1997 + A1:2003 + A2:2007.

INSTALLATION

Location

The power supply must be sited indoors on a dry, flat surface in an area that is well ventilated. Ideally the panel
indicators should be at eye level and the ambient light level should allow the status of the indicators to be clearly seen.

Mounting

Using  the  five  mounting  holes  provided,  mount  the  metal  base  securely  onto  a  wall.  Assess  the  condition  and
construction of the wall and use suitable screw fixings. The mounting holes are suitable for use with No.8-10 or
4-5 mm countersunk screws. Any dust or swarf created during the mounting process must be kept out of the enclosure
and care must be taken not to damage any wiring or components.

Wiring and Cable Entry

All wiring should be installed in accordance with the current edition of the IEE Wiring Regs
(BS 7671), or the relevant national standards. The requirement for the Mains supply to the
panel is fixed wiring, using 3-core cable (no less than 1 mm

2

and no greater than 2.5 mm

2

),

or a suitable three conductor system fed from an isolating switched spur fused at 3 A.
In order to maintain cable segregation the incoming Mains cable should be fed into the
panel via the top centre knockouts (provided on the metal base). Knockouts should be
removed with a sharp, light tap using a flat 6 mm broadsided screwdriver, as shown in the
diagram (see right). Always ensure that if a knockout is removed, the hole is filled with a
good quality 20 mm cable gland. Any unused knockouts must be securely blanked off.

WARNING: DO NOT ATTEMPT TO CONNECT THE MAINS SUPPLY TO THE POWER
SUPPLY PCB UNLESS ALL COMPONENTS ARE SECURELY INSTALLED IN THE ENCLOSURE.

Terminate the Mains cable at the Power Supply connector block CONN1 (see Figure 1 below).

RPF0361000 Rev2

Temp

Display

Black-  Red+

BATTERY 
FUSE
F2
F5A

CONN4

0V Charge

Off

C    NC   NO
Fault Relay

No Batteries

PLK1

PLK2

Fit for 5.5 to 18Ahr
Not fitted for 1.6 to 5.5Ahr

PL2

RLY1

CONN3

Output

C10

C10

+

+

+

+

CONN5

0V

+V

VR1
DO NOT
ADJUST

C6

C6

PL1

PL3

T2AH 250V
HRC

PRIMARY
FUSE  F1

LED MUST
EXTINGUISH
BEFORE 
SERVICE

C1

TX1

C11

C11

D7

D7

R24

R24

Battery

C24

C24

C20

C20

C23

C23

C31

C31

Mains Input Terminals (CONN1)

L = Live, N = Neutral,      = Earth

CLASS 1 EQUIPMENT MUST BE EARTHED.

Connect incoming Mains earth wire
to the earth terminal and NOT to the
base earth post.

PSU Earth Strap

DO NOT operate this equipment
without connecting this strap to the
base earth post.

Display Connector (PL1)

High Temp. Output (PL2)

Charge Off Input (CONN4)

Incoming Mains Cable

Must be segregated from other
cables and only enter the panel
through the top central knockouts.

Hazardous Voltages Present LED

When lit red, hazardous voltages
are present on the components
and copper in the hashed area of
the PCB. 

DO NOT TOUCH!

Supply Output (CONN5)

Battery Input (CONN5)

Figure 1 - Power Supply PCB Layout and Connection Details

Battery Charge Current Link (PLK2)

Fault Relay (CONN3)

Battery Monitoring Link (PLK1)

If batteries NOT used, fit PLK1 link.

See Technical Specification
overleaf for further details

0786-CPD-20892