7-42
Inputs, Outputs, Timers, and Other Control Logic
Date Code 20011205
SEL-311B Instruction Manual
Text settings (remain the same for all setting groups):
DP1_1 = 79 ENABLED
(displayed when DP1 = logical 1)
DP1_0 = 79 DISABLED
(displayed when DP1 = logical 0)
Because SEL
OGIC
control equation display point setting DP1 is always at logical 0, the
corresponding text setting DP1_0 continually displays in the rotating default displays:
79 DISABLED
Additional Rotating Default Display Example
See Figure 5.4 and accompanying text in
Section 5: Trip and Target Logic
for an example of
resetting a rotating default display with the TARGET RESET pushbutton.
Displaying Time-Overcurrent Elements on the Rotating Default Display
The LCD can display the pickup settings for the time-overcurrent elements in primary units via a
special character sequence in the display points equations. As with the previously described
display points, the operator does not need to press any buttons to see this information.
To program a display point to show the pickup setting of a time-overcurrent element, first enter
the two-character sequence “::” (double colon) followed by the name of the desired time-
overcurrent element pickup settings for 51PP, 51GP, or 51QP.
For example with the factory default settings for 51PP and CTR, setting DP1_0 = ::51PP will
display
1200.00 A pri
.
The relay calculates the value to display by multiplying the 51PP setting (6.00 A secondary) by
the CTR setting (200), arriving at 1200.00 A primary. The relay displays the display point
DP1_0 because the factory default SEL
OGIC
control equation DP1 = 0 (logical 0).
The calculations for the remaining time-overcurrent elements are similar, except for 51GP which
is multiplied by the CTRP setting.
If the display point setting does not match the format correctly, the relay will display the setting
text string as it was actually entered, without substituting the time-overcurrent element setting
value.
Displaying Time-Overcurrent Elements Example
This example demonstrates use of the rotating display to show time-overcurrent elements in
primary units. This example will set the 51PP and 51GP to display in the rotating default
display.
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......