12-10
Standard Event Reports and SER
Date Code 20011205
SEL-311B Instruction Manual
Table 12.3: Output, Input, and Protection, and Control Element Event Report Columns
Column
Heading
Corresponding
Elements (Relay
Word Bits)
Symbol
Definition
All columns
.
Element/input/output not picked up or
not asserted, unless otherwise stated.
ZAB
1
MAB1
MAB2
MAB3
1
2
3
If Zone 1 AB phase-phase distance
element (MAB1) set
If Zone 2 AB phase-phase distance
element (MAB2) set, not ZAB1
If Zone 3 AB phase-phase distance
element (MAB3) set, not ZAB1 or
ZAB2
Z PP
2
MPP1
MPP2
MPP3
1
2
3
If Zone 1 phase-phase distance
element (MPP1) set
If Zone 2 phase-phase distance
element (MPP2) set, not ZPP1
If Zone 3 phase-phase distance
element (MPP2) set, not ZPP1 or
ZPP2
ZBC
1
MBC1
MBC2
MBC3
1
2
3
If Zone 1 BC phase-phase distance
element (MBC1) set
If Zone 2 BC phase-phase distance
element (MBC2) set, not ZBC1
If Zone 3 BC phase-phase distance
element (MBC3) set, not ZBC1 or
ZBC2
Z 3P
2
MABC1
MABC2
MABC3
1
2
3
If Zone 1 3-phase distance element
(MABC1) set
If Zone 2 3-phase distance element
(MABC2) set, not Z3P1
If Zone 3 3-phase distance element
(MABC3) set, not Z3P1 or Z3P2
ZCA
1
MCA1
MCA2
MCA3
1
2
3
If Zone 1 CA phase-phase distance
element (MCA1) set
If Zone 2 CA phase-phase distance
element (MCA2) set, not ZCA1
If Zone 3 CA phase-phase distance
element (MCA3) set, not ZCA1 or
ZCA2
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......