8-20
Breaker Monitor and Metering Functions
Date Code 20011205
SEL-311B Instruction Manual
The SEL-311B Relay provides demand and peak demand metering for the following values:
Currents I
A,B,C
I
G
3I
2
Input currents (A primary)
Residual ground current (A primary; I
G
=3I
0
= I
A
+ I
B
+ I
C
)
Negative-sequence current (A primary)
Power MW
A,B,C,3P
MVAR
A,B,C,3P
Single- and three-phase megawatts
Single- and three-phase megavars
Depending on enable setting EDEM, these demand and peak demand values are thermal demand
or rolling demand values. The differences between thermal and rolling demand metering are
explained in the following discussion.
Comparison of Thermal and Rolling Demand Meters
The example in Figure 8.11 shows the response of thermal and rolling demand meters to a step
current input. The current input is at a magnitude of zero and then suddenly goes to an
instantaneous level of 1.0 per unit (a “step”).
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......