Date Code 20011205
Setting the Relay
9-19
SEL----311B Instruction Manual
Row
Bit
Definition
Primary
Application
67G2T
Level 2 residual ground definite-time overcurrent
element 67G2T timed out (derived from 67G2; see
Figure 3.16)
50G3
Level 3 residual ground instantaneous overcurrent
element (residual ground current above pickup
setting 50G3P; see Figure 3.16)
67G3
Level 3 torque controlled residual ground
instantaneous overcurrent element (derived from
50G3; see Figure 3.16)
67G3T
Level 3 residual ground definite-time overcurrent
element 67G3T timed out (derived from 67G3; see
Figure 3.16)
*
*
28
51P
Maximum phase current above pickup setting 51PP
for phase time-overcurrent element 51PT (see
Figure 3.18)
Testing, Control
51PT
Phase time-overcurrent element 51PT timed out (see
Figure 3.18)
Tripping
51PR
Phase time-overcurrent element 51PT reset (see
Figure 3.18)
Testing
Z1X
Zone 1 extension element picked up (see
Figure 3.11)
Indication
59VA
Channel VA voltage window element (channel VA
voltage between threshold settings 25VLO and
25VHI; see Figure 3.24)
MAB3
Mho AB phase distance zone 3 instantaneous (see
Figure 3.6)
Testing
MBC3
Mho BC phase distance zone 3, instantaneous (see
Figure 3.6)
MCA3
Mho CA phase distance zone 3, instantaneous (see
Figure 3.6)
29
MAG3
Mho ground distance A-phase, zone 3 (see
Figure 3.9)
MBG3
Mho ground distance B-phase, zone 3 (see
Figure 3.9)
MCG3
Mho ground distance C-phase, zone 3 (see
Figure 3.9)
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......