Date Code 20011205
Inputs, Outputs, Timers, and Other Control Logic
7-7
SEL-311B Instruction Manual
Figure 7.5: Local Control Switch Configured as an OFF/MOMENTARY Switch
ON/OFF/MOMENTARY Switch
The local bit LB
n
:
is in either the ON (LB
n
= logical 1) or OFF (LB
n
= logical 0) position
or
is in the OFF (LB
n
= logical 0) position and pulses to the MOMENTARY (LB
n
= logical 1)
position for one processing interval (1/4 cycle).
Figure 7.6: Local Control Switch Configured as an ON/OFF/MOMENTARY Switch
Table 7.2: Correspondence Between Local Control Switch Types
and Required Label Settings
Local Switch Type
Label NLB
n
Label
CLB
n
Label
SLB
n
Label
PLB
n
ON/OFF
X X X
OFF/MOMENTARY X X X
ON/OFF/MOMENTARY
X X X X